Work report — Austin & Central Texas
Concrete Tile Roof: Roof-to-Wall Leak
An isolated repair, documented start to finish.
What failed. The leak was traced to the roof-to-wall transition on the side of the house. At the lower wall there was no metal flashing — foam and mortar had been used in its place. Rain landing on that wall face ran down it and entered the assembly at the junction instead of being discharged back onto the roof. Beneath the tile, the underlayment was past its service life, brittle and no longer continuous, so there was no second line behind the missing flashing. The channel at the transition was packed with debris and nesting material, which kept the area wet between rains rather than letting it dry. Water followed the framing into the deck edge, fascia and soffit, and from there to the ceiling inside. The sheathing at the wall line had absorbed water long enough to delaminate.
What we did. Opened the section, removed the compromised material, and rebuilt the detail: new deck, self-adhered underlayment, formed metal wall flashing, battens re-set, and the home’s original tile reinstalled.
The photographs below are in the order the work was done, beginning with the interior condition that was reported. Documented on site by the owner. Client name and address withheld.
The repair, in order
























Recap
What was there, what replaced it, and why the assembly performs differently now.
| Detail | Condition found | Rebuilt as — and the reason |
|---|---|---|
| Lower wall junction | No metal flashing; foam and mortar in its place. Wall runoff entered at the junction and tracked into the deck edge, fascia and soffit. | Formed metal flashing, lapped over the membrane and discharging onto the tile surface, so the wall’s runoff is returned to the roof. Foam and sealant fill a gap but carry nothing — and they shrink with age. |
| Underlayment | Original underlayment, brittle and torn; no continuous barrier beneath the tile. | Self-adhered membrane bonded to the deck, sealing around every fastener driven through it. Tile sheds water; the membrane is what keeps it out. |
| Deck | Sheathing saturated and delaminated; would not hold a fastener. | New sheathing to sound framing, so battens and flashing anchor into solid material. |
| Drainage channel | Packed with debris and nesting material, holding water against the deck between rains. | Cleared, with batten drainage space restored so water beneath the tile exits rather than standing. |
| Tile | Intact. Concrete tile typically outlasts everything beneath it. | Removed by hand and reinstalled — decades of weathering that new stock cannot match. |
Follow-up on this job
We returned after the repair to look at the section and check with the homeowner, who reported no further water inside. The underlayment replaced here was original to the roof; the same original underlayment remains beneath the tile outside the repaired area, on the same service-life clock — and we said so.
Scope note. This was a repair to a defined section of roof. Conditions not opened were not inspected.
About this report. These photographs were taken during this project and show selected stages of the work. This report records what was done on this job and what was found. It is not an inspection certification, a condition report, or a warranty, and it does not add to or change the scope of any agreement. Scope, materials and methods on any project are set by that project’s signed estimate and contract. Conditions not opened were not inspected, and nothing here is a warranty or guarantee of future performance on any other property.
Tile roofs rarely fail at the tile. They fail at the flashings and the underlayment beneath it. See a full tile replacement on a counter-batten system, or our roof repair services.