Building science, not guesswork

Attic ventilation, done right.

Most roofers treat ventilation as an afterthought — or oversell it as an energy miracle. Here's what it actually does, what the building science really says, and exactly how we spec it on your roof.

The honest version

What it does — and what it doesn't.

What ventilation does

Controls moisture — the main job. It dries the roof deck and keeps humidity from building up, which is what prevents mold, rot, and premature deck and shingle failure.

Sheds some heat. A well-vented attic runs cooler and takes strain off your AC and shingles — a real, but modest, benefit.

What it doesn't do

It's not a big energy-bill fix. Building-science field studies show a vented roof deck runs only a few degrees cooler than an unvented one. We won't promise dramatic cooling savings.

It can't fix a leaky ceiling. If house air is pouring up into your attic, ventilation is just managing a problem created below it.

The honest version: Ventilation protects your roof deck and controls moisture, and it gives you some heat relief. The bigger energy lever is sealing your ceiling and ducts — which is why we'll always tell you what we see up there.
What actually matters, in order

Most roofers obsess over vent count. Here's what really matters.

This is the priority the building science actually supports — and it's mostly the opposite of how ventilation gets sold.

1

Air-seal the attic floor

Stop household air — and the moisture it carries — from leaking up through the ceiling at can lights, top plates, chases, the attic hatch, and leaky ducts. This is the highest-leverage move, and most roofers never mention it.

2

Balance it, intake-biased

Keep intake (low, at the eaves) at least equal to — ideally a hair more than — exhaust (high, at the ridge). A healthy attic never pulls conditioned air out of the house below it.

3

Size it, and keep the path clear

Hit the vent area the code requires, and make sure air can actually travel from soffit to ridge — with baffles holding the channel open the whole way.

Why this order matters: a vented attic over an air-sealed floor is one of the most reliable assemblies in building science. When one fails, it's almost always step 1 that got skipped — not the vent math.
The #1 real-world problem

Balance is what actually breaks roofs.

You can hit the total vent numbers and still have a bad system if intake and exhaust aren't matched.

Intake ≥ exhaust

Run intake at least equal to exhaust — ideally a touch higher — so the attic stays gently balanced and never sucks conditioned air out of your ceiling.

Never let exhaust exceed intake

An exhaust-heavy attic pulls makeup air backward through its own vents — dragging weather in and starving whole sections of the roof.

What we find most: the problem is rarely too few ridge vents — it's starved intake: painted-over soffits, insulation stuffed into the eaves, too few intake vents. Fixing the intake is usually the highest-leverage move on the whole roof.
How an attic breathes

Cool air in low. Hot, moist air out high.

An attic breathes like a body: cool, dry air comes in low at the eaves (intake) and hot, moist air rises and leaves high at the ridge and hips (exhaust). The vents only manage what's already up there — which is why sealing the ceiling below comes first.

LIVING SPACEATTICair-sealed ceiling (step 1)cool incool inhot, moist air out
Soffit intake → ridge/hip exhaust, over an air-sealed, insulated ceiling.
Transparency

We measure and math it. We don't guess.

Code sets the minimum — one square foot of open vent for every 150 or 300 square feet of attic floor, depending on the system. But "meets code on paper" doesn't mean it works: a vent combo can miss the required open area once you do the real math on net free area — the actual open hole after louvers and mesh. So on every job we measure your attic, calculate what it needs, show you what you have, and show you the gap — before we install anything.

Worked example — 2,000 sq ft attic
1
Needed (balanced system): 2,000 ÷ 300 × 144 = 960 sq in of net free area.
2
Split it: ~480 sq in intake (low) and ~480 sq in exhaust (high), biased slightly toward intake.
3
Translate to product, then verify on the roof. The numbers do the selling — not a sales pitch.
How we build it

The rules we never break.

Seal first.Air-seal the attic floor before you count on any vent.
Size it.Calculate the real net free area the attic requires.
Split it, intake-biased.Half low, half high — with a little extra toward intake.
Never over-exhaust.Exhaust must never exceed intake.
One exhaust type.No mixing ridge, box, turbine, or gable on one attic.
Keep the path clear.Baffles in every intake bay, soffit to ridge.
Complex & hip roofs

We vent the attic, not the deck.

On a cut-up roof — lots of hips, valleys, and dormers — trying to vent the roof deck continuously is nearly impossible. Venting the attic (soffit → ridge and hips) works no matter how complex the roof is; the geometry simply doesn't matter for attic venting. On the hip roofs common in Central Texas, a conforming ridge vent that runs along the hips is the answer.

Honest scope

What we install — and what we'll tell you about.

Ours to install & stand behind

Exhaust — one type, no mixing; our go-to is the Owens Corning VentSure ridge/hip vent.

Intake — soffit and eave vents sized to match.

A clear airflow path — baffles in the intake bays, and no over-exhausting or open gables left to short-circuit the system.

We'll flag, inform, or refer

Air-sealing the attic floor — the biggest lever, and we'll always point out what we see.

Leaky or uninsulated ductwork in the attic, and thin insulation depth.

Whether an unvented / spray-foam approach makes more sense for your home.

Thoroughness without overreach. We fix what's ours to fix, and we're honest about the rest — even when it isn't work we're selling.
The system we trust

Owens Corning VentSure.

We standardize on the VentSure line because one family of products covers ridge, hips, and intake, with an external baffle that keeps wind-driven rain out. On the cut-up hip roofs common here, the VentSure strip conforms to any roof angle and runs continuously along the ridge and hips as one clean exhaust system — paired with matched intake at the eaves. One exhaust type, sized to your attic, weather-resistant.

Ready when you are

Let's see how your attic is really breathing.

A free inspection includes a real read on your ventilation — what you have, what it needs, and an honest look at what's actually driving heat and moisture in your home.

Grounded in IRC R806.2 & R806.3 (minimum vent area and roof-deck venting), Building Science Corporation research on attic ventilation (Joseph Lstiburek), and Owens Corning VentSure manufacturer data. We confirm current product specs and local code amendments on every job.  See our full References & Sources.